Solar Drive Forward and Reverse Setup
For a EM12 SP Drive or EM15 SP Drive with Single Line keypad the Reverse function is only possible while PV Mode is switched Off. In order to do this the following is required:
- Connect a Rocker Switch to DI1 (for FWD) and DI2 (for REV) – see VSD FWD/REV setup as example HERE.
- Bridge DI2 and DI3
- Set F0-02 = 1 (Terminal Control)
- Set F4-00 = 1 (DI1 = FWD: the default is set to 1)
- Set F4-01 = 2 (DI2 = REV: before being able to set this, first set F4-05=0)
- Set F4-02 = 53 (DI3 = Stop PV Mode: the default is set to 53)
* Note that the FWD/REV feature is not applicable for Single-Phase Motors (unless when using a Three Wire setup without Capacitors).
* For a EM15 SP Drive with Double Line keypad the Reverse function is possible while in PV Mode, ensure b2-15 = 0 to activate the Reverse functionality.