How to perform Soft Starter Error 4 Troubleshooting

| 0

Soft Starter Error 4 Troubleshooting

Error 4 Reasons (for a GW Series Soft Starter):

  1. Input Power Source Voltage is not Balanced
    • Check the 3-Phase Input Voltages
  2. A possible Settings Problem
    • Can restore factory settings
  3. Thyristors’ main circuit or control circuit problems
    • There are 3 groups of red and white cables
    • One group has 2 red and white cables
    • Test the resistance between each group’s red and white cable (~ 10V but up to 20V fine)
    • Use buzzer position – one probe to R and one to U (S to V and T to W)
  4. Control Board Problems
    • Check that the control board light is blinking
  5. Transformer Voltage
    • Measure the transformer voltage
    • There are 6 small cables
    • Two yellow cables voltage should be about 18v to 20V
    • Two green cable voltage should be about 9V

 