Axial Flow Fan Selection
For Soft Starter Cooling/Panel Fan Selection, please see the relevant FAQ page HERE.
The following 3 tables lists all the available axial flow fans and their respective specifications:
Please note that the D-Series 380V Fans can also be used with a Single-Phase 230V supply, with the following adjusted CFM and RPM values:
- D1: CFM = 23 and RPM = 1500
- D2: CFM = 189 and RPM = 1600
To determine the required cooling (CFM) for a specific panel, use the VSD kW * 5.364 to calculate the required CFM value and select the appropriate fan/s accordingly. Please see table below showing the appropriate fan/s selection for each specific kW option VSD.