How to Setup a T-Series VSD for Synchronous Motors

| 0

T-Series VSD Setup

Set the following parameters when installing a T-Series VSD for Synchronous Motors:

Motor Parameters:

  • b0-00 = 2 (Motor type set to synchronous motor)
  • b0-13 = Set as motor nameplate (Maximum frequency)
  • b0-15 = Set as motor nameplate (Frequency upper limit)
  • d0-00 = Set as motor nameplate (Motor rated power)
  • d0-01 = Set as motor nameplate (Motor rated voltage)
  • d0-02 = Set as motor nameplate (Motor rated current)
  • d0-03 = Set as motor nameplate (Motor rated frequency)
  • d0-04 = Set as motor nameplate (Motor rated speed)

Motor Control Mode:

  • b0-01 = 0 (Open-loop vector control)

Motor Auto Tuning:

  • If the Motor can be disconnected from the load: Set d0-30 = 12 (dynamic no-load auto tuning), press RUN and wait for about 20s to complete the auto tuning process.
  • If the Motor cannot be disconnected from the load: Set d0-30 = 11 (static auto tuning), press RUN and wait for about 10s to complete the auto tuning process.

If oscillation occurs during operation, the vector control parameter gain parameters (d1-01 ~ d1-05) can be adjusted (for parameter descriptions, please refer to the EM15 series manual). Increase Proportional Gain and decrease Integral Time to increase the gain. The acceleration and deceleration time b0-21 and b0-22 can also be adjusted (generally does not need to be adjusted).

 