VSD Forward and Reverse Jogging
To setup a Forward and Reverse Jogging function for a drive a Toggle Switch can be used (see image below for wiring) with the following parameter settings:
- Set b0-02 = 1 (Terminal Control) – This is to ensure the Start/Stop functions are triggered via the Terminal Controls (Normal Start/Stop function will also require an external on/off switch).
- Set b3-03 = 4 (To set DI4 as the Forward JOG terminal)
- Set b3-04 = 5 (To set DI5 as the Reverse JOG terminal)
- Set b2-00 = User Defined Value (Default value for JOG speed = 2Hz)
- Set b2-01 = User Defined Value (Default JOG Acceleration time is model dependant)
- Set b2-02 = User Defined Value (Default JOG Deceleration time is model dependant)