How to Setup an External Fault Device to Stop a VSD

| 0

VSD External Fault Setup

Setup an External Fault Device to Stop a VSD (but still use Keypad Start/Stop function):

From the External Device, connect the Normally Open or Normally Closed wire with DI1 and connect the Common wire with Common and then set:

  • If it is a Normally Open connection:
    • b3-00 = 38 (default = 01)
  • If it is a Normally Closed connection:
    • b3-00 = 39 (default = 01)

 

In this scenario, keep b0-02 = 0 (Default: Keypad Control) to allow for the VSD to Start/Stop using the VSD keypad. If the External device Stops the VSD the VSD will show Err15 which indicates that the external fault device caused the VSD to stop.

 